ABB i-bus
®
KNX
Group objects
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 332
8.6
Group objects Channel – General
No.
Function
Group object name Data Type
Flag
46
Forced operation 2 bit
Channel – General
2 bits
DPT 2.001
C, W
This group object is enabled if the parameter
Use forced operation
is set to
Forced operation 2 bit
in the
Monitoring and safety
parameter window.
This group object activates and deactivates forced operation.
Telegram value
(bit 1 | bit 0: Status Forced operation):
•
0 | 0: Forced operation inactive
•
0 | 1: Forced operation inactive
•
1 | 0: Forced operation active; state OFF
•
1 | 1: Forced operation active; state ON
47
Forced operation 1 bit
Channel – General
1 bit
DPT 1.002
C, W
The group object is enabled if the parameter
Use forced operation
is set to
Forced operation1 bit
,
0 active
or
Forced operation1 bit
,
1 active
in the
Monitoring and safety
parameter window.
This group object activates and deactivates forced operation.
Depending on the selected option, forced operation is activated with a 1 or 0 and deactivated with a 0 or 1.
48
Error: heating/cooling receipt
Channel – General
1 bit
DPT 1.002
C, R, T
This group object is enabled if the parameter
Monitor receipt of group object "Toggle heating/cooling"
is set
to
Activated
in the
Monitoring and safety
parameter window.
This group object changes to the value 1 if the parametrized monitoring time was exceeded without a value
being received on the group object.
The status changes back to 0 when the group object is received again.
The group object is sent on each state change (0 > 1 or 1 > 0).
49
Error: window status receipt
Channel – General
1 bit
DPT 1.002
C, R, T
This group object is enabled if the parameter
Monitor receipt of group object "Window contact"
is set to
Acti-
vated
in the
Monitoring and safety
parameter window.
This group object changes to the value 1 if the parametrized monitoring time was exceeded without the
group object being received.
The status changes back to 0 when the group object is received again.
The group object is sent on each state change (0 > 1 or 1 > 0).
50
Error: dew point status receipt
Channel – General
1 bit
DPT 1.002
C, R, T
This group object is enabled if the parameter
Monitor receipt of group object "Dew point alarm"
is set to
Acti-
vated
in the
Monitoring and safety
parameter window.
This group object changes to the value 1 if the parametrized monitoring time was exceeded without the
group object being received.
The status changes back to 0 when the group object is received again.
The group object is sent on each state change (0 > 1 or 1 > 0).
51
Error: fill level status receipt
Channel – General
1 bit
DPT 1.002
C, R, T
This group object is enabled if the parameter
Monitor receipt of group object "Fill level alarm"
is set to
Acti-
vated
in the
Monitoring and safety
window.
This group object changes to the value 1 if the parametrized monitoring time was exceeded without the
group object being received.
The status changes back to 0 when the group object is received again.
The group object is sent on each state change (0 > 1 or 1 > 0).