ABB i-bus
®
KNX
Product Overview
3.11.4.6
Rated current output 16 A
Rated values
Number
1
U
n2
rated voltage
250 V AC (50/60 Hz)
I
n2
rated current (per output pair)
16 A (resistive load for additional heater)
Switching currents
AC3* operation (cos ϕ = 0.45) to EN 60947-4-1 16 A / 230 V AC
AC1* operation (cos ϕ = 0.8) to EN 60947-4-1
16 A / 230 V AC
Minimum switching capacity at 100 mA
24 V AC
DC current switching capacity, resistive load, at
16 A
24 V DC
Service life
Mechanical service life
> 3 x 10⁶ cycles
Electrical endurance of switching contacts to
IEC 60947-4-1
> 10⁶ cycles
AC1* (240 V/cos ϕ=0.8)
> 10⁵ cycles
Switching times
Maximum relay position change per output and
minute if only one relay is switched.
> 500
3.11.4.7
Fan output (analog)
Rated values
Number
1, non-isolated, short-circuit proofed
Control signal
0…10 V DC
Signal type
Analog
Output load
> 10 kohms
Output tolerance
± 10%
Current limitation
max. 1.5 mA
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 77