Description of application and parameters
Application "1-button blind"
KNX Technical Reference Manual 1473-1-8905 / 2CKA001473B8905
│30
10.5.3 General parameters - Object type
Options:
1 bit
1 byte 0 - 100%
Via the parameter object type, you can specify whether the blind control occurs via two 1-bit or
two 1-byte communication objects "Move" and "Adjust".
If 1-byte was selected as object type, the communication objects can be connected with 1-byte
position objects from blind actuators. For example: One side of the button could lower the blind
to 50% with slats closed 50%, while the other button side can lower the blind to 80% with slats
closed 100%.
10.5.4 Extended parameters — Switchover of function blind/roller shutter
Options:
Blind
Roller shutter
The "Function switchover blinds/roller shutters" specifies whether a blind or roller shutter is to be
driven by a button operation. With the "Roller shutter" setting, the value for the slats adjustment
does not apply.
10.5.5 Extended parameters - Value for position Down (%)
NOTE
This parameter is only visible if the "Function switchover blinds/roller shutters"
parameter is set on blind.
Options:
0 ... 100
The position that a connected blind is to be lowered to is set via this parameter. The associated
1-byte "Move" communication object must hereby be connected with a 1-byte position object of
a blind actuator. Percentage values from 0% to 100% can be set in 1% steps. The value 0%
means travel up completely; the value 100% means travel down completely.