Description of application and parameters
Application "1-button step switch"
KNX Technical Reference Manual 1473-1-8905 / 2CKA001473B8905
│48
10.9
Application "1-button step switch"
NOTE
The application is valid for the following parts of the device:
■
Button 1 / rocker 1
■
Button 2
■
Button 3 / rocker 2
■
Button 4
Different switching processes are triggered with each new actuation of the 1st or 2nd button.
For example:
■
First actuation (2nd button) switches on lamp 1.
■
Second actuation (2nd button) switches lamp 1 off and lamp 2 on.
■
Third actuation (2nd button) switches lamp 2 off and lamp 3 on.
■
Fourth actuation (1st button) switches lamp 3 off and lamp 2 on.
■
Fifth actuation (1st button) switches lamp 2 off and lamp 1 on.
■
etc.
Up to five switching levels can be activated.
The application differentiates between whether the 1st or 2nd button was actuated. Depending
on the setting, one lower or one higher level can be switched to.
10.9.1 General parameters - Number of objects
Options:
1 … 5
The application can switch up to five levels. For every level, its own 1-bit communication object
is available. The number of the levels is specified via the "Number of objects" parameter.
10.9.2 General parameters for - Evaluation period
Options:
02.000 ... 05.000
The application can differentiate between a single, double, triple, quadruple or quintuple
operation of the button.
If the button is to recognise a multiple operation, then the button must be operated multiple
times in a relatively short period of time. The period during which the button evaluates a multiple
operation is started anew after each operation.