Description of application and parameters
Application "2-button step switch"
KNX Technical Reference Manual 1473-1-8905 / 2CKA001473B8905
│71
10.18.3 Extended parameters - Working mode of the buttons
Options:
1st button down / 2nd button up
1st button up / 2nd button down
The "Working mode of the buttons" is used to specify whether an operation of the left or right
side of the button will send out a travel up or travel down telegram.
10.18.4 Extended parameters — Sending of objects
Options:
For change of value
For operation
The parameter "Sending of objects" specifies whether the object values for every button
operation are sent out or only if the object values have changed since the last sending out.
10.18.5 Extended parameters - Object values
Options:
Normal
Inverse
The object values can be sent "normal" or "inverse" via their associated 1-bit communication
objects. If the parameter "Object values" is set to "inverse" then all 1-bit communication objects
of the individual levels send out their values inverted.
10.18.6 Extended parameters - Bit pattern of object values
Options:
x of n
1 of n
The levels can be switched in two different bit patterns:
x of n (for 5 objects, object 0 to 4)
1 of n (for 5 objects, object 0 to 4)
00000
10000
11000
11100
11110
11111
00000
10000
01000
00100
00010
00001