Description of application and parameters
Application "1-button switching" as primary function
KNX Technical Reference Manual 1473-1-8905 / 2CKA001473B8905
│85
10.21.4 General parameters - Value 1
NOTE
This parameter is only visible if the "Reaction at rising/falling edge" parameter is
set on either "Value 1" or "Alternating Value1/Value2".
Options:
Dependent on the setting of the "Object type" parameter (see the
following).
Value 1 is specified here which is sent out at a long operation of the button. This is dependent
on the setting of the "Object type" parameter.
Settings:
–
1 bit
: On/Off
–
1 byte 0 - 100%
: arbitrary values from 0 to 100%
–
1 byte 0 - 255
: arbitrary values from 0 to 255
–
Light scene number 1 - 64
: specifying light scene numbers from 1 to 64
–
RTC operating mode switchover (1 byte)
: auto / comfort / standby / ECO /
frost-/heat protection
10.21.5 General parameters - Value 2
NOTE
This parameter is only visible if the "Reaction at rising/falling edge" parameter is
set on either "Value 2" or "Alternating Value1/Value2".
Options:
Dependent on the setting of the "Object type" parameter (see the
following).
Value 2 is specified here which is sent out at a long operation of the button. This is dependent
on the setting of the "Object type" parameter.
Settings:
–
1 bit
: On/Off
–
1 byte 0 - 100%
: arbitrary values from 0 to 100%
–
1 byte 0 - 255
: arbitrary values from 0 to 255
–
Light scene number 1 - 64
: specifying light scene numbers from 1 to 64
–
RTC operating mode switchover (1 byte)
: auto / comfort / standby / ECO /
frost-/heat protection