ABB i-bus
®
KNX
Safety
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 13
2.7
Connection to the Internet
KNXnet/IP routing and KNXnet/IP tunneling use unencrypted data transfer and is therefore not intended
for use on the public internet. For this reason router ports in the direction of the internet must not be
opened: this action will ensure KNX communication is not visible on the internet.
Systems can be accessed via the internet in the following ways:
•
Access to KNX installations via VPN connections. However, this requires a router with VPN server
functionality or a server.
•
Use of manufacturer-specific solutions or visualizations, e.g. access via https.
2.8
Open IP network ports
The device uses the following network ports for data communication in the IP network. It is to be ensured
that only authorized systems have access to these network ports.
Port
Limitation
Protocol
Remark
27360 TCP
20/minute
SSH
Only if SSH access has been
activated
1900 TCP
15/second
i-bus
®
Tool
80, 443 TCP
15/second
http, https
WebUI
123 UDP
20/second
NTP
Only if NTP is activated
47808 UDP
30/second
BACnet
Only if BACnet is activated.
The port can be changed.
3671 TCP+UDP
30/second
KNX
For the KNX download
2403 TCP
30/second
Automation ASM
Monitor mode.
Only if access has been activated.
Table 2: Open IP network ports
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 476: ......
Page 482: ......
Page 484: ...ABB i bus KNX Appendix 484 2CDC508198D0211 Rev A AC S 1 x 1 13 2 Notes ...
Page 485: ...ABB i bus KNX Appendix AC S 1 x 1 2CDC508198D0211 Rev A 485 Notes ...
Page 486: ...ABB i bus KNX Appendix 486 2CDC508198D0211 Rev A AC S 1 x 1 Notes ...
Page 487: ......