ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 171
Send cyclically values to KNX
Options:
No (checkbox cleared)
Yes (checkbox selected)
This parameter specifies whether the value is to be sent cyclically on the KNX bus.
•
No (checkbox cleared):
The value is only sent on the KNX bus after a change.
•
Yes (checkbox selected):
The value is sent on the KNX bus after every change and cyclically.
The cycle time is set in the
Send cyclically values to KNX every
parameter below and is
restarted each time on sending after a change.
Selection of
Yes
option:
Dependent parameter(s)
Send cyclically values to KNX every
Options:
00:10:00…01:00:00…23:59:00 [hh:mm:ss]
Selection of
Input
or
Input + output
option:
Dependent parameter(s)
Read value at startup
Options:
No (checkbox cleared)
Yes (checkbox selected)
•
No (checkbox cleared):
The value is only sent on the KNX bus after a change.
•
Yes (checkbox selected):
The value is sent on the KNX bus after every change and cyclically.
The cycle time is set in the
Send cyclically values to KNX every
parameter below and is
restarted each time on sending after a change.
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 476: ......
Page 482: ......
Page 484: ...ABB i bus KNX Appendix 484 2CDC508198D0211 Rev A AC S 1 x 1 13 2 Notes ...
Page 485: ...ABB i bus KNX Appendix AC S 1 x 1 2CDC508198D0211 Rev A 485 Notes ...
Page 486: ...ABB i bus KNX Appendix 486 2CDC508198D0211 Rev A AC S 1 x 1 Notes ...
Page 487: ......