ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 187
Controller On/Off
Options:
None
Display
set (slave)
This parameter specifies whether the On/Off status of the room thermostat received via KNX is only to be
displayed on the web user interface, or it can also be changed by the user. The current value is output on
the ASM output socket and in a BACnet object.
•
None:
The On/Off status of the room thermostat is not used in the module and can therefore not be
displayed on the web user interface.
•
Display:
The On/Off status of the room thermostat from KNX is displayed on the web user interface.
The current value is output on the ASM output socket and in a BACnet object
•
set (slave):
The room thermostat can be switched on or off via the web user interface. The
command is sent via KNX to the room thermostat. The current value is output on the ASM output
socket and in a BACnet object.
This setting functions only with ABB and Busch-Jaeger devices with the old master/slave interface
Heating/cooling operating type
Options:
None
Display
set (slave)
This parameter specifies whether the heating/cooling operating type from the room thermostat received via
KNX is only to be displayed on the web user interface, or it can also be changed by the user. The current
value is output on the ASM output socket and in a BACnet object.
•
None:
The heating/cooling operating type is not used in the module; this operating type is therefore
not displayed on the web user interface.
•
Display:
The heating/cooling operating type from KNX is displayed on the web user interface. The
current value is output on the ASM output socket and in a BACnet object.
•
set (slave):
The heating/cooling operating type can be changed on the web user interface and
is sent via KNX. The current value is output on the ASM output socket and in a BACnet object.
This setting functions only with ABB and Busch-Jaeger devices with the old master/slave interface
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 476: ......
Page 482: ......
Page 484: ...ABB i bus KNX Appendix 484 2CDC508198D0211 Rev A AC S 1 x 1 13 2 Notes ...
Page 485: ...ABB i bus KNX Appendix AC S 1 x 1 2CDC508198D0211 Rev A 485 Notes ...
Page 486: ...ABB i bus KNX Appendix 486 2CDC508198D0211 Rev A AC S 1 x 1 Notes ...
Page 487: ......