AC/S 1.x.1 | 2CDC508198D0211 Rev. A 189
Rel. humidity
Options:
No (checkbox cleared)
Yes (checkbox selected)
This parameter specifies whether the value measured for the relative humidity in the room is displayed on
the web user interface and is to be output in the BACnet object and on the ASM output socket.
CO2 value
Options:
No (checkbox cleared)
Yes (checkbox selected)
This parameter specifies whether the value measured for the air quality in the room is displayed on the
web user interface as a CO
2
value and is to be output in the BACnet object and on the ASM output socket.
Fan coil unit
Options:
None
2-pipe heating
2-pipe cooling
2-pipe heating/cooling
4-pipe h cooling
Selects the fan coil unit (blower convector). The type selected affects the depiction on the web user
interface and the number of valve control values.
•
None:
A fan coil unit is not used in the room.
•
2-pipe heating:
The fan coil unit can only heat
•
2-pipe cooling:
The fan coil unit can only cool
•
2-pipe heating/cooling:
The fan coil unit can heat and cool. It is only connected via 2 pipes that contain
hot or cold water depending on the central operating type. It is therefore only ever possible to heat or
cool; a central changeover is necessary to change.
•
4-pipe h cooling:
The fan coil unit can heat and cool. In a 4-pipe system, separate pipes are
used for the hot and cold water supply. It is therefore possible to change between heating and cooling
at any time. As such the room thermostat can select the heating/cooling operating type as required.
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 476: ......
Page 482: ......
Page 484: ...ABB i bus KNX Appendix 484 2CDC508198D0211 Rev A AC S 1 x 1 13 2 Notes ...
Page 485: ...ABB i bus KNX Appendix AC S 1 x 1 2CDC508198D0211 Rev A 485 Notes ...
Page 486: ...ABB i bus KNX Appendix 486 2CDC508198D0211 Rev A AC S 1 x 1 Notes ...
Page 487: ......