ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 211
Object function
Name (can be changed
separately)
Data type
Flags
Input: Fan coil unit, valve cooling
Room
1 byte
DPT 5.001
C, W, T, U
The module has this group object if the
2-pipe cooling
option or the
4-pipe h cooling
option is selected for the
parameter.
Input for the valve position (control value) on the fan coil unit for cooling.
Telegram value:
0…100%
Input: Fan coil unit, valve
Room
1 byte
DPT 5.001
C, W, T, U
The module has this group object if the
2-pipe heating/cooling
option is selected for the
parameter.
Input for the valve position (control value) on the fan coil unit. This is for either heating or cooling depending on the
heating/cooling operating type.
Telegram value:
0…100%
Input: Fan coil unit, fan speed
Room
1 byte
DPT 5.001
C, W, T, U
The module has this group object if any option except
None
is selected for the
parameter and the
Display
option
is selected for the
Input for the fan speed on the fan coil unit.
Telegram value:
0…100%
Input: Fan coil unit, fan manual
Room
1 bit
DPT 1.011
C, W, T, U
The module has this group object if any option except
None
is selected for the
parameter and the
Display
option
is selected for the
Input for the connection of the status from the room thermostat as to whether the current fan speed has been adjusted
manually by a user or it was calculated automatically by the room thermostat.
Telegram value:
0 = Automatic
1 = Manual
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 476: ......
Page 482: ......
Page 484: ...ABB i bus KNX Appendix 484 2CDC508198D0211 Rev A AC S 1 x 1 13 2 Notes ...
Page 485: ...ABB i bus KNX Appendix AC S 1 x 1 2CDC508198D0211 Rev A 485 Notes ...
Page 486: ...ABB i bus KNX Appendix 486 2CDC508198D0211 Rev A AC S 1 x 1 Notes ...
Page 487: ......