ABB i-bus
®
KNX
Parameters
212 2CDC508198D0211 Rev. A | AC/S 1.x.1
Object function
Name (can be changed
separately)
Data type
Flags
Input: Fan coil unit, fan speed confirm (slave)
Room
1 byte DPT 5.001
1 byte DPT 5.010
C, W, T, U
This group object is used for synchronization of the fan speed status between the Room ASM (slave) and the room thermostat
(master). For this purpose the group object must be connected to the controller's (master's) group object of the same name.
In this group object the room thermostat (master) confirms the change in the fan speed to the Room ASM (slave).
The data point type for the group object is dependent on the settings in the module:
•
If any option except
None
is selected for the
set (slave) DPT 5.001
option is
selected for the
parameter:
DPT 5.001
Telegram value 0…100 %
The fan speed in percent is transmitted, e.g. 50 %. Fan speeds are converted into the corresponding percentage.
•
If any option except
None
is selected for the
set (slave) DPT 5.010
option is
selected for the
parameter:
DPT 5.010
Telegram value 0 … 5
The fan speed is transmitted
Input: Fan coil unit, fan manual confirm (slave)
Room
1 bit
DPT 1.011
C, W, T, U
The module has this group object if any option except
None
is selected for the
parameter and the
set
(slave) DPT 5.001
option or
Set (Slave) DPT 5.010
option is selected for the
This group object is used for synchronization of the fan speed status between the Room ASM (slave) and the room thermostat
(master). For this purpose the group object must be connected to the controller's (master's) group object of the same name.
In this group object the room thermostat (master) confirms to the Room ASM (slave) whether the current fan speed has been
adjusted manually by a user or it was calculated automatically by the room thermostat.
Telegram value:
0 = Automatic
1 = Manual
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 476: ......
Page 482: ......
Page 484: ...ABB i bus KNX Appendix 484 2CDC508198D0211 Rev A AC S 1 x 1 13 2 Notes ...
Page 485: ...ABB i bus KNX Appendix AC S 1 x 1 2CDC508198D0211 Rev A 485 Notes ...
Page 486: ...ABB i bus KNX Appendix 486 2CDC508198D0211 Rev A AC S 1 x 1 Notes ...
Page 487: ......