AC/S 1.x.1 | 2CDC508198D0211 Rev. A 215
Object function
Name (can be changed
separately)
Data type
Flags
Input: Fan coil unit, level sensor
Room
1 bit
DPT 1.001
C, W, T, U
The module has this group object if any option except
None
is selected for the
parameter and the
Yes
option is
selected for the
Fan coil unit, level sensor
parameter.
Input for the signal value from the level sensor in the fan coil unit.
Telegram value:
0 = Off
1 = On
Input: Radiator, valve
Room
1 bit DPT 1.001
1 byte DPT 5.001
C, W, T, U
Input for the position (control value) of the radiator valve.
The data point type for the group object is dependent on the settings in the module:
•
If the
On/Off
option is selected for the
parameter:
DPT 1.001
Telegram value 0 = Off, 1 = On
•
If the
0…100 %
option is selected for the
DPT 5.001
Telegram value 0…100 %
Input: Floor heating, valve
Room
1 bit DPT 1.001
1 byte DPT 5.001
C, W, T, U
Input for the position (control value) of the floor heating valve.
The data point type for the group object is dependent on the settings in the module:
•
If the
On/Off
option is selected for the
parameter:
DPT 1.001
Telegram value 0 = Off, 1 = On
•
If the
0…100 %
option is selected for the
DPT 5.001
Telegram value 0…100 %
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 476: ......
Page 482: ......
Page 484: ...ABB i bus KNX Appendix 484 2CDC508198D0211 Rev A AC S 1 x 1 13 2 Notes ...
Page 485: ...ABB i bus KNX Appendix AC S 1 x 1 2CDC508198D0211 Rev A 485 Notes ...
Page 486: ...ABB i bus KNX Appendix 486 2CDC508198D0211 Rev A AC S 1 x 1 Notes ...
Page 487: ......