ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 223
Object name
Object type
Unit
COV send
condition
Room: Fan coil unit, dew point sensor
Binary value
-
-
The module has this BACnet output object if any option except
None
is selected for the
parameter and the
Yes
option is selected for the
Fan coil unit, dew point sensor
parameter.
Outputs the signal value from the dew point sensor in the fan coil unit.
Signal value:
0 = Off
1 = On
Fan coil unit, level sensor
Binary value
-
-
The module has this BACnet output object if any option except
None
is selected for the
parameter and the
Yes
option is selected for the
Fan coil unit, level sensor
parameter.
Outputs the signal value from the level sensor in the fan coil unit.
Signal value:
0 = Off
1 = On
Room: Radiator, valve
Binary value
Analog value
-
% (98)
-
1.0
Outputs the position of the radiator valve.
The object type for the object is dependent on the settings in the module:
•
If the
On/Off
option is selected for the
parameter:
Object type binary value
Unit –
Send condition –
Signal value 0 = Off, 1 = On
•
If the
0…100 %
option is selected for the
Object type analog value
Unit % (98)
Send condition 1.0
Signal value 0…100 %
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 476: ......
Page 482: ......
Page 484: ...ABB i bus KNX Appendix 484 2CDC508198D0211 Rev A AC S 1 x 1 13 2 Notes ...
Page 485: ...ABB i bus KNX Appendix AC S 1 x 1 2CDC508198D0211 Rev A 485 Notes ...
Page 486: ...ABB i bus KNX Appendix 486 2CDC508198D0211 Rev A AC S 1 x 1 Notes ...
Page 487: ......