ABB i-bus
®
KNX
Parameters
224 2CDC508198D0211 Rev. A | AC/S 1.x.1
Object name
Object type
Unit
COV send
condition
Room: Floor heating, valve
Binary value
Analog value
-
% (98)
-
1.0
Outputs the position of the floor heating valve.
The object type for the object is dependent on the settings in the module:
•
If the
On/Off
option is selected for the
parameter:
Object type binary value
Unit –
Send condition –
Signal value 0 = Off, 1 = On
•
If the
0…100 %
option is selected for the
parameter:
Object type analog value
Unit % (98)
Send condition 1.0
Signal value 0…100 %
Room: Floor temperature sensor
Analog value
°C (62)
1.0
The module has this BACnet output object if the
On/Off
option or the
0…100 %
option is selected for the
parameter and the
Yes
option is selected for the
Floor temperature sensor
parameter.
Outputs the floor temperature.
Signal value:
-273...670760 °C
Room: Cooling ceiling, valve
Binary value
Analog value
-
% (98)
-
1.0
Outputs the position of the cooling ceiling valve.
The object type for the object is dependent on the settings in the module:
•
If the
On/Off
option is selected for the
Object type binary value
Unit –
Send condition –
Signal value 0 = Off, 1 = On
•
If the
0…100 %
option is selected for the
Object type analog value
Unit % (98)
Send condition 1.0
Signal value 0…100 %
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 476: ......
Page 482: ......
Page 484: ...ABB i bus KNX Appendix 484 2CDC508198D0211 Rev A AC S 1 x 1 13 2 Notes ...
Page 485: ...ABB i bus KNX Appendix AC S 1 x 1 2CDC508198D0211 Rev A 485 Notes ...
Page 486: ...ABB i bus KNX Appendix 486 2CDC508198D0211 Rev A AC S 1 x 1 Notes ...
Page 487: ......