Dead band between heating and cooling
Options:
0…3…10 °C (calculated dynamically)
Using the dead band, a minimum spacing between the room setpoint temperatures can be set for heating
and cooling. This value is defined in °C and applies between all room setpoint temperatures for heating
and cooling, independent of the operating modes. Using this dead band it can be ensured that a controller
does not change continuously between heating and cooling.
If only heating or only cooing is activated, this setting has no effect. If the dead zone is set to 0 °C, this
function is deactivated.
The dead zone cannot be set via the web user interface.
Send cyclically values to KNX every
Options:
00:10:00…06:00:00…23:59:00 [hh:mm:ss]
The room setpoint temperatures are sent immediately on the KNX bus after every change on the web user
interface. In addition, using this setting all room setpoint temperatures activated can be sent again
cyclically on the KNX bus. The cycle time is restarted each time a value change is sent.
It is not possible to deactivate the cyclic sending.
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 476: ......
Page 482: ......
Page 484: ...ABB i bus KNX Appendix 484 2CDC508198D0211 Rev A AC S 1 x 1 13 2 Notes ...
Page 485: ...ABB i bus KNX Appendix AC S 1 x 1 2CDC508198D0211 Rev A 485 Notes ...
Page 486: ...ABB i bus KNX Appendix 486 2CDC508198D0211 Rev A AC S 1 x 1 Notes ...
Page 487: ......