ABB i-bus
®
KNX
Parameters
248 2CDC508198D0211 Rev. A | AC/S 1.x.1
Radiator exponent
Options:
None/Linear (1.0)
Floor heating (1.05)
Floor heating (1.10)
Flat radiators (1.20)
Flat radiators (1.25)
Radiator to DIN 4703 (1.30)
Flat radiators (1.33)
Convectors (1.35)
Convectors (1.40)
Convectors (1.45)
Convectors (1.50)
The radiator exponent is dependent on the type and design of the heating element
and is normally stated by the manufacturer. The radiator exponent describes the
relationship between the increasing supply temperature and the non-proportionally
increasing heat dissipation into the room.
This information is used to calculate the heating curve. The higher this value is, the
more curved the heating curve is.
Start supply temperature curve at outside temperature
Options:
-100…19…100 °C
The outside temperature at which heating is started is specified using this parameter.
This value is the start of the heating curve. The heating limit is dependent on the
insulation standards in the building and can be selected lower, the better the building
is insulated.
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 476: ......
Page 482: ......
Page 484: ...ABB i bus KNX Appendix 484 2CDC508198D0211 Rev A AC S 1 x 1 13 2 Notes ...
Page 485: ...ABB i bus KNX Appendix AC S 1 x 1 2CDC508198D0211 Rev A 485 Notes ...
Page 486: ...ABB i bus KNX Appendix 486 2CDC508198D0211 Rev A AC S 1 x 1 Notes ...
Page 487: ......