ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 281
Object name
Object type
Unit
COV send
condition
Heating distribution circuit: Control On/Off override disable/enable
Binary value
-
-
The module has this BACnet output object in the following conditions:
•
If the
Yes
option is selected for the
Supply temperature control
parameter and the
Yes
option is selected for the
heating distribution circuit control based on ASM input socket
parameter.
•
If the
Yes
option is selected for the
Switch off if no room demand
parameter.
Outputs whether the control (Off/On) for the heating distribution circuit controller has been overridden via the web user
interface.
Signal value:
0 = Not overridden
1 = Overridden
Heating distribution circuit: Room control values
Analog value
% (98)
1.0
The module has this BACnet output object in the following conditions:
•
If the
Yes
option is selected for the
parameter, the
Calculated weather compensated
option is
selected for the
Supply setpoint temperature source
parameter and the
Yes
option is selected for the
parameter.
•
If the
Yes
option is selected for the
Outputs the highest room setpoint temperature that is present on the ASM input socket and that is used by the
Economy mode
and
Switch off if no room demand
functions.
Signal value:
0…100 %
Heating distribution circuit: Pump A override disable/enable
Binary value
-
-
The module has this BACnet output object if the
Yes
option is selected for the
Outputs whether the heating distribution circuit's pump is overridden.
Signal value:
0 = Disabled
1 = Enabled
Heating distribution circuit: Pump A override value
Binary value
-
-
The module has this BACnet output object
if the
Yes
option is selected for the
This object specifies the state with which the heating distribution circuit's pump is overridden if the pump override is active.
Signal value:
0 = Off
1 = On
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 476: ......
Page 482: ......
Page 484: ...ABB i bus KNX Appendix 484 2CDC508198D0211 Rev A AC S 1 x 1 13 2 Notes ...
Page 485: ...ABB i bus KNX Appendix AC S 1 x 1 2CDC508198D0211 Rev A 485 Notes ...
Page 486: ...ABB i bus KNX Appendix 486 2CDC508198D0211 Rev A AC S 1 x 1 Notes ...
Page 487: ......