ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 285
Object name
Object type
Unit
COV send
condition
Heating distribution circuit: Valve override control value
Analog value
% (98)
1.0
The module has this BACnet output object
if the
3-way valve (mixing valve)
option or the
2-way valve
option is selected for the
Yes
option is selected for the
parameter.
Outputs the value used to override the heating distribution circuit's valve if the override is active.
Signal value:
0…100 %
Heating distribution circuit: Status Valve purge
Binary value
-
-
The module has this BACnet output object
if the
3-way valve (mixing valve)
option or the
2-way valve
option is selected for the
Yes
option is selected for the
parameter.
Outputs the status as to whether the heating distribution circuit controller is actually undertaking a valve purge. This value is
received from the heating distribution circuit controller linked via the related module group object.
Signal value:
0 = Inactive
1 = Active
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 476: ......
Page 482: ......
Page 484: ...ABB i bus KNX Appendix 484 2CDC508198D0211 Rev A AC S 1 x 1 13 2 Notes ...
Page 485: ...ABB i bus KNX Appendix AC S 1 x 1 2CDC508198D0211 Rev A 485 Notes ...
Page 486: ...ABB i bus KNX Appendix 486 2CDC508198D0211 Rev A AC S 1 x 1 Notes ...
Page 487: ......