ABB i-bus
®
KNX
Parameters
316 2CDC508198D0211 Rev. A | AC/S 1.x.1
Object name
Data type
Pump fault
DPT 1.005
The module has this output socket if the
Yes
option is selected for the
Pump display pump fault status
Outputs the fault status provided by the pump.
Signal value:
0 = No alarm
1 = Alarm
Pump repair switch status
DPT 1.011
The module has this output socket if the
Yes
option is selected for the
Display pump repair switch status
Outputs the contact position provided by the pump repair switch.
Signal value:
0 = Inactive
1 = Active
Pump override disable/enable
DPT 1.003
The module has this output socket if the
Yes
option is selected for the
Outputs whether the heat generator's pump is overridden.
Signal value:
0 = Disabled
1 = Enabled
Pump override value
DPT 1.001
The module has this output socket if the
Yes
option is selected for the
Outputs the state with which the heat generator's pump is overridden if the pump override is active.
Signal value:
0 = Off
1 = On
Supply setpoint temperature
DPT 9.001
The module has this output socket if the
Yes
option is selected for the
parameter.
Outputs the current supply setpoint temperature as is sent by the module to the heat generator via the related group object.
The supply setpoint temperature output here is, depending on the setting, either calculated by this module based on the
outside temperature, or specified via an ASM input socket or BACnet and also takes into account any possible override of the
supply setpoint temperature via the web user interface.
Signal value:
-273...670760 °C
Supply setpoint temperature External specification
DPT 9.001
This module has this output socket if the
Yes
option is selected for the
parameter and the
BACnet
input object
option is selected for the
Supply setpoint temperature source
Outputs the supply setpoint temperature specified via the BACnet object. This status does not take into account any possible
override of the supply setpoint temperature via the web user interface.
Signal value:
-273...670760 °C
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 476: ......
Page 482: ......
Page 484: ...ABB i bus KNX Appendix 484 2CDC508198D0211 Rev A AC S 1 x 1 13 2 Notes ...
Page 485: ...ABB i bus KNX Appendix AC S 1 x 1 2CDC508198D0211 Rev A 485 Notes ...
Page 486: ...ABB i bus KNX Appendix 486 2CDC508198D0211 Rev A AC S 1 x 1 Notes ...
Page 487: ......