ABB i-bus
®
KNX
Parameters
318 2CDC508198D0211 Rev. A | AC/S 1.x.1
7.10.4
Group objects
Object function
Name (can be
changed
separately)
Data point type
(DPT)
Length
Flags
C R W T U I
Input: Supply temperature
Heat generator
9.001
2 bytes
x
x x
Input: Return temperature
Heat generator
9.001
2 bytes
x
x x
Output: Supply setpoint temperature
Heat generator
9.001
2 bytes
x x
x
Input: Pump relay status
Heat generator
1.001
1 bit
x
x x
Output: Heat generator On/Off
Heat generator
1.001
1 bit
x x
x
Input: Heat generator operating status
Heat generator
1.011
1 bit
x
x x
Input: Heat generator failure status
Heat generator
1.011
1 bit
x
x x
In-/Output: Pump override disable/enable
Heat generator
1.003
1 bit
x x x x
In-/Output: Pump override value
Heat generator
1.001
1 bit
x x x x
Input: Pump operating status (Off/On)
Heat generator
1.011
1 bit
x
x x
Input: Pump fault
Heat generator
1.011
1 bit
x
x x
Input: Pump repair switch status
Heat generator
1.011
1 bit
x
x x
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 476: ......
Page 482: ......
Page 484: ...ABB i bus KNX Appendix 484 2CDC508198D0211 Rev A AC S 1 x 1 13 2 Notes ...
Page 485: ...ABB i bus KNX Appendix AC S 1 x 1 2CDC508198D0211 Rev A 485 Notes ...
Page 486: ...ABB i bus KNX Appendix 486 2CDC508198D0211 Rev A AC S 1 x 1 Notes ...
Page 487: ......