ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 323
BACnet input objects
Object name
Object type
Unit
COV send
condition
Heat generator: Supply setpoint temperature External specification
Analog value
°C (62)
-
This module has this BACnet input object if the
Yes
option is selected for the
parameter and the
BACnet input object
option is selected for the
Supply setpoint temperature source
parameter.
Input for the specification of the supply setpoint temperature. The value is sent by the module to the heat generator via the
related group object. This supply setpoint temperature specified via BACnet can be overridden manually on the web user
interface.
Signal value:
-273...670760 °C
BACnet output objects
Object name
Object type
Unit
COV send
condition
Heat generator: Return temperature
Analog value
°C (62)
1.0
Outputs the current return temperature that is received via the related group object.
Signal value:
-273...670760 °C
Heat generator: Supply temperature
Analog value
°C (62)
1.0
Outputs the current supply temperature that is received via the related group object.
Signal value:
-273...670760 °C
Heat generator: Supply setpoint temperature status
Analog value
°C (62)
1.0
The module has this BACnet output object if the
Yes
option is selected for the
parameter.
Outputs the current supply setpoint temperature as is sent by this module to the heat generator via the related group object.
The supply setpoint temperature output here is, depending on the settings, either calculated by this module based on the
outside temperature, or specified via an ASM input socket or BACnet and also takes into account any possible override of the
supply setpoint temperature via the web user interface.
Signal value:
-273...670760 °C
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...