Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 341
Selection of
ASM input socket
or
BACnet input object
option:
Dependent parameter(s):
Supply setpoint temperature offset
Options:
0…100 °C
An offset can be entered to compensate for the energy losses in the pipes. This value is
always subtracted from the supply setpoint temperature and is limited by the
Min. supply
temperature
parameter.
Selection of
WebUI Input
or
BACnet input object
option:
Dependent parameter(s):
Initial values
Supply setpoint temperature
Options:
0…10…100 °C
This parameter defines the supply setpoint temperature that is output after downloading the
module. This value is output until a new value is entered on the web user interface or is
written to the BACnet object. This value is limited by the
Min. supply temperature
parameter.