ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 357
Object function
Name (can be changed separately)
Data type
Flags
In-/Output: Valve override disable/enable Cooling distribution circuit
1 bit
DPT 1.003
C, R, W, T
The module has this group object
if the
3-way valve (mixing valve)
option or the
2-way valve
option is selected for the
parameter and the
Yes
option is selected for the
This object activates/deactivates the valve (mixing valve) override for the cooling distribution circuit controller.
Telegram value:
0 = Disabled
1 = Enabled
In-/Output: Valve override control value
Cooling distribution circuit
1 byte
DPT 5.001
C, R, W, T
The module has this group object
if the
3-way valve (mixing valve)
option or the
2-way valve
option is selected for the
parameter and the
Yes
option is selected for the
This object specifies the control value (valve position) used to override the valve for the cooling distribution circuit if the valve
override is active.
Telegram value:
0…100 %
Input: Status Valve purge
Cooling distribution circuit
1 bit
DPT 1.011
C, W, T
The module has this group object
if the
3-way valve (mixing valve)
option or the
2-way valve
option is selected for the
parameter and the
Yes
option is selected for the
parameter.
Input for the status of the cooling distribution circuit controller as to whether a valve purge is currently in progress.
Telegram value:
0 = Inactive
1 = Active
Input: Pump A repair switch status
Cooling distribution circuit
1 bit
DPT 1.011
C, W, T
The module has this group object
if the
Yes
option is selected for the
Display pump repair switch status
parameter.
The status of the repair switch for the pump can be received via this group object and evaluated by the device.
Telegram value:
0 = Inactive
1 = Active
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 476: ......
Page 482: ......
Page 484: ...ABB i bus KNX Appendix 484 2CDC508198D0211 Rev A AC S 1 x 1 13 2 Notes ...
Page 485: ...ABB i bus KNX Appendix AC S 1 x 1 2CDC508198D0211 Rev A 485 Notes ...
Page 486: ...ABB i bus KNX Appendix 486 2CDC508198D0211 Rev A AC S 1 x 1 Notes ...
Page 487: ......