ABB i-bus
®
KNX
Parameters
358 2CDC508198D0211 Rev. A | AC/S 1.x.1
Object function
Name (can be changed separately)
Data type
Flags
Input: Pump A fault
Cooling distribution circuit
1 bit
DPT 1.011
C, W, T
The module has this group object
if the
Yes
option is selected for the
Pump display pump fault status
parameter.
The fault state of the pump can be received via this group object and evaluated by the device
Telegram value:
0 = Inactive
1 = Active
Input: Pump A operating status (Off/On)
Cooling distribution circuit
1 bit
DPT 1.011
C, W, T
The module has this group object if the
Yes
option is selected for the
Input for the operating status (Off/On) provided by the pump. On pumps with their own control, this operating status can differ
from the operating status of the cooling distribution circuit controller.
Telegram value:
0 = Inactive
1 = Active
In-/Output: Pump A override
disable/enable
Cooling distribution circuit
1 bit
DPT 1.003
C, R, W, T
The module has this group object
if the
Yes
option is selected for the
This object activates/deactivates the pump override for the cooling distribution circuit controller.
Telegram value:
0 = Disabled
1 = Enabled
In-/Output: Pump A override value
Cooling distribution circuit
1 bit
DPT 1.001
C, R, W, T
The module has this group object
if the
Yes
option is selected for the
This object specifies the state with which the pump for the cooling distribution circuit is overridden if the pump override is
active.
Telegram value:
0 = Off
1 = On
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 476: ......
Page 482: ......
Page 484: ...ABB i bus KNX Appendix 484 2CDC508198D0211 Rev A AC S 1 x 1 13 2 Notes ...
Page 485: ...ABB i bus KNX Appendix AC S 1 x 1 2CDC508198D0211 Rev A 485 Notes ...
Page 486: ...ABB i bus KNX Appendix 486 2CDC508198D0211 Rev A AC S 1 x 1 Notes ...
Page 487: ......