ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 359
Object function
Name (can be changed separately)
Data type
Flags
Input: Pump B fault
Cooling distribution circuit
1 bit
DPT 1.011
C, W, T
The module has this group object
if the
Yes
option is selected for the
Yes
option is selected
for the
Pump display pump fault status
parameter.
The fault state of the second pump can be received via this group object and evaluated by the device
Telegram value:
0 = Inactive
1 = Active
In-/Output: Pump B override
disable/enable
Cooling distribution circuit
1 bit
DPT 1.003
C, R, W, T
The module has this group object
if the
Yes
option is selected for the
Yes
option is selected
for the
This object activates/deactivates the second pump override for the cooling distribution circuit controller.
Telegram value:
0 = Disabled
1 = Enabled
In-/Output: Pump B override value
Cooling distribution circuit
1 bit
DPT 1.001
C, R, W, T
The module has this group object
if the
Yes
option is selected for the
Yes
option is selected
for the
This object specifies the state with which the second pump for the cooling distribution circuit is overridden if the second pump
override is active.
Telegram value:
0 = Off
1 = On
Input: Pump B repair switch status
Cooling distribution circuit
1 bit
DPT 1.011
C, W, T
The module has this group object
if the
Yes
option is selected for the
Yes
option is selected
for the
Display pump repair switch status
The status of the repair switch for the second pump can be received via this group object and evaluated by the device.
Telegram value:
0 = Inactive
1 = Active
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 476: ......
Page 482: ......
Page 484: ...ABB i bus KNX Appendix 484 2CDC508198D0211 Rev A AC S 1 x 1 13 2 Notes ...
Page 485: ...ABB i bus KNX Appendix AC S 1 x 1 2CDC508198D0211 Rev A 485 Notes ...
Page 486: ...ABB i bus KNX Appendix 486 2CDC508198D0211 Rev A AC S 1 x 1 Notes ...
Page 487: ......