AC/S 1.x.1 | 2CDC508198D0211 Rev. A 361
7.11.5
BACnet objects
Type
Object name
Object type
Unit
COV send
condition
Input
Cooling distribution circuit: Supply setpoint temperature External
specification
Analog value
°C (62)
-
Output
Cooling distribution circuit: Return temperature
Analog value
°C (62)
1.0
Output
Cooling distribution circuit: Supply temperature
Analog value
°C (62)
1.0
Output
Cooling distribution circuit: Supply setpoint temperature status
Analog value
°C (62)
1.0
Output
Cooling distribution circuit: Outside temperature
Analog value
°C (62)
1.0
Output
Cooling distribution circuit: Supply setpoint temperature override
status
Binary value
-
-
Output
Cooling distribution circuit: Supply setpoint temperature External
specification
Analog value
°C (62)
1.0
Output
Cooling distribution circuit: Control On/Off
Binary value
-
-
Output
Cooling distribution circuit: Control On/Off override disable/enable
Binary value
-
-
Output
Cooling distribution circuit: Room control values
Analog value
% (98)
1.0
Output
Cooling distribution circuit: Pump A override disable/enable
Binary value
-
-
Output
Cooling distribution circuit: Pump A override value
Binary value
-
-
Output
Cooling distribution circuit: Pump A operating status (Off/On)
Binary value
-
-
Output
Cooling distribution circuit: Pump A relay status
Binary value
-
-
Output
Cooling distribution circuit: Pump A fault
Binary value
-
-
Output
Cooling distribution circuit: Pump A repair switch status
Binary value
-
-
Output
Cooling distribution circuit: Pump B override disable/enable
Binary value
-
-
Output
Cooling distribution circuit: Pump B override value
Binary value
-
-
Output
Cooling distribution circuit: Pump B operating status (Off/On)
Binary value
-
-
Output
Cooling distribution circuit: Pump B relay status
Binary value
-
-
Output
Cooling distribution circuit: Pump B fault
Binary value
-
-
Output
Cooling distribution circuit: Pump B repair switch status
Binary value
-
-
Output
Cooling distribution circuit: Valve control value
Analog value
% (98)
1.0
Output
Cooling distribution circuit: Valve override disable/enable
Binary value
-
-
Output
Cooling distribution circuit: Valve override control value
Analog value
% (98)
1.0
Output
Cooling distribution circuit: Status Valve purge
Binary value
-
-
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 476: ......
Page 482: ......
Page 484: ...ABB i bus KNX Appendix 484 2CDC508198D0211 Rev A AC S 1 x 1 13 2 Notes ...
Page 485: ...ABB i bus KNX Appendix AC S 1 x 1 2CDC508198D0211 Rev A 485 Notes ...
Page 486: ...ABB i bus KNX Appendix 486 2CDC508198D0211 Rev A AC S 1 x 1 Notes ...
Page 487: ......