ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 365
Object name
Object type
Unit
COV send
condition
Cooling distribution circuit: Pump A operating status (Off/On)
Binary value
-
-
The module has this BACnet output object if the
Yes
option is selected for the
Outputs the operating status (Off/On) provided by the pump. On pumps with their own control, this operating status can differ
from the operating status of the cooling distribution circuit controller.
Signal value:
0 = Inactive
1 = Active
Cooling distribution circuit: Pump A relay status
Binary value
-
-
Outputs the status of the cooling distribution circuit controller's pump.
Signal value:
0 = Off
1 = On
Cooling distribution circuit: Pump A fault
Binary value
-
-
The module has this BACnet output object
if the
Yes
option is selected for the
Pump display pump fault status
parameter.
Outputs the fault status provided by the pump.
Signal value:
0 = Inactive
1 = Active
Cooling distribution circuit: Pump A repair switch status
Binary value
-
-
The module has this BACnet output object
if the
Yes
option is selected for the
Display pump repair switch status
Outputs the contact position provided by the pump repair switch.
Signal value:
0 = Inactive
1 = Active
Cooling distribution circuit: Pump B override disable/enable
Binary value
-
-
The module has this BACnet output object
if the
Yes
option is selected for the
parameter and the
Yes
option is
selected for the
Outputs whether the second pump for the cooling distribution circuit is overridden.
Signal value:
0 = Disabled
1 = Enabled
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 476: ......
Page 482: ......
Page 484: ...ABB i bus KNX Appendix 484 2CDC508198D0211 Rev A AC S 1 x 1 13 2 Notes ...
Page 485: ...ABB i bus KNX Appendix AC S 1 x 1 2CDC508198D0211 Rev A 485 Notes ...
Page 486: ...ABB i bus KNX Appendix 486 2CDC508198D0211 Rev A AC S 1 x 1 Notes ...
Page 487: ......