Parameters
370 2CDC508198D0211 Rev. A | AC/S 1.x.1
This section displays the state of the pump from the cooling distribution circuit controller linked. If a double
pump has been activated in the settings, a second section with the label "Pump B" appears. The settings
described here for "Pump A" apply correspondingly to the section for "Pump B".
If activated in the settings, the pump for the cooling distribution circuit controller can be overridden by the
"admin" and "expert" users via the web user interface. For this purpose the slider must be dragged to one
of the two "Override" positions.
Status Pump relay
Outputs the status of the pump from the cooling distribution circuit controller linked.
Pump operating status
Outputs the operating status (Off/On) provided by the pump. On pumps with their own control, this
operating status can differ from the operating status of the cooling distribution circuit controller.
Pump fault
Outputs the fault status provided by the pump.
Repair switch
Outputs the contact position provided by the pump repair switch.
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 476: ......
Page 482: ......
Page 484: ...ABB i bus KNX Appendix 484 2CDC508198D0211 Rev A AC S 1 x 1 13 2 Notes ...
Page 485: ...ABB i bus KNX Appendix AC S 1 x 1 2CDC508198D0211 Rev A 485 Notes ...
Page 486: ...ABB i bus KNX Appendix 486 2CDC508198D0211 Rev A AC S 1 x 1 Notes ...
Page 487: ......