ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 381
Pump
Settings for the chiller's pump.
Pump
Options:
No (checkbox cleared)
Yes (checkbox selected)
This parameter specifies whether a pump is used in the cooling system. The group objects, BACnet
objects, ASM sockets and the depiction on the web user interface are adjusted to suit the setting.
Override by WebUI
Options:
No (checkbox cleared)
Yes (checkbox selected)
If this function is activated, the pump can be overridden via the web user interface. For this purpose
additional group objects are displayed that must be connected to the chiller.
Pump display operating status
Options:
No (checkbox cleared)
Yes (checkbox selected)
If the pump outputs its operating status (Off/On), this status can be received by a group object via this
function and output on the web user interface, in a BACnet object and on the ASM socket.