ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 387
Object name
Data type
Supply setpoint temperature
DPT 9.001
The module has this output socket if the
Yes
option is selected for the
Outputs the current supply setpoint temperature as is sent by the module to the chiller via the related group object. The supply
setpoint temperature output here is, depending on the setting, either calculated by this module based on the outside
temperature, or specified via an ASM input socket or BACnet and also takes into account any possible override of the supply
setpoint temperature via the web user interface.
Signal value:
-273...670760 °C
Supply setpoint temperature External specification
DPT 9.001
This module has this output socket if the
Yes
option is selected for the
BACnet
input object
option is selected for the
Supply setpoint temperature source
parameter.
Outputs the supply setpoint temperature specified via the BACnet object. This status does not take into account any possible
override of the supply setpoint temperature via the web user interface.
Signal value:
-273...670760 °C
Chiller operating status
DPT 1.001
The module has this output socket if the
Yes
option is selected for the
parameter.
Outputs the operating status (Off/On) provided by the chiller. Due to the control integrated into the chiller, this status may differ
from the operating status specified by this module.
Signal value:
0 = Off
1 = On
Chiller fault status
DPT 1.001
The module has this output socket if the
Yes
option is selected for the
parameter.
Outputs the fault status provided by the chiller.
Signal value:
0 = Off
1 = On
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 476: ......
Page 482: ......
Page 484: ...ABB i bus KNX Appendix 484 2CDC508198D0211 Rev A AC S 1 x 1 13 2 Notes ...
Page 485: ...ABB i bus KNX Appendix AC S 1 x 1 2CDC508198D0211 Rev A 485 Notes ...
Page 486: ...ABB i bus KNX Appendix 486 2CDC508198D0211 Rev A AC S 1 x 1 Notes ...
Page 487: ......