BACnet objects
Type
Object name
Object type
Unit
COV send
condition
Input
Chiller: Supply setpoint temperature External specification
Analog value
°C (62)
-
Output
Chiller: Return temperature
Analog value
°C (62)
1.0
Output
Chiller: Supply temperature
Analog value
°C (62)
1.0
Output
Chiller: Supply setpoint temperature status
Analog value
°C (62)
1.0
Output
Chiller: Outside temperature
Analog value
°C (62)
1.0
Output
Chiller: Supply setpoint temperature override status
Binary value
-
-
Output
Chiller: Supply setpoint temperature External specification
Analog value
°C (62)
1.0
Output
Chiller: Chiller On/Off
Binary value
-
-
Output
Chiller: Control On/Off override disable/enable
Binary value
-
-
Output
Chiller: Chiller operating status
Binary value
-
-
Output
Chiller: Chiller fault status
Binary value
-
-
Output
Chiller: Room control values
Analog value
% (98)
1.0
Output
Chiller: Pump override disable/enable
Binary value
-
-
Output
Chiller: Pump override value
Binary value
-
-
Output
Chiller: Pump operating status (Off/On)
Binary value
-
-
Output
Chiller: Pump relay status
Binary value
-
-
Output
Chiller: Pump fault
Binary value
-
-
Output
Chiller: Pump repair switch status
Binary value
-
-
BACnet input objects
Object name
Object type
Unit
COV send
condition
Chiller: Supply setpoint temperature External specification
Analog value
°C (62)
-
This module has this BACnet input object if the
Yes
option is selected for the
BACnet input object
option is selected for the
Supply setpoint temperature source
Input for the specification of the supply setpoint temperature. The value is sent by the module to the chiller via the related
group object. This supply setpoint temperature specified via BACnet can be overridden manually on the web user interface.
Signal value:
-273...670760 °C
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 476: ......
Page 482: ......
Page 484: ...ABB i bus KNX Appendix 484 2CDC508198D0211 Rev A AC S 1 x 1 13 2 Notes ...
Page 485: ...ABB i bus KNX Appendix AC S 1 x 1 2CDC508198D0211 Rev A 485 Notes ...
Page 486: ...ABB i bus KNX Appendix 486 2CDC508198D0211 Rev A AC S 1 x 1 Notes ...
Page 487: ......