ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 407
7.13.4
Group objects
Object function
Name (can be
changed separately)
Data point
type (DPT)
Length
Flags
C R W T U I
Output: Operating type
Heating/cooling
changeover
1.100
1 bit
x
x
x
Output: Heating
Heating/cooling
changeover
1.001
1 bit
x
x
x
Output: Cooling
Heating/cooling
changeover
1.001
1 bit
x
x
x
Object function
Name (can be changed separately)
Data type
Flags
Output: Operating type
Heating/cooling changeover
1 bit
DPT 1.100
C, R, T
Outputs the active operating type. The value is sent on every change and then repeated every 30 minutes. The cycle time
cannot be changed.
Telegram value:
0 = Cooling
1 = Heating
Output: Heating
Heating/cooling changeover
1 bit
DPT 1.001
C, R, T
Outputs the state of the heating operating type. The value is sent on every change and then repeated every 30 minutes. The
cycle time cannot be changed.
Telegram value:
0 = Off
1 = On
Output: Cooling
Heating/cooling changeover
1 bit
DPT 1.001
C, R, T
Outputs the state of the heating operating type. The value is sent on every change and then repeated every 30 minutes. The
cycle time cannot be changed.
Telegram value:
0 = Off
1 = On
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 476: ......
Page 482: ......
Page 484: ...ABB i bus KNX Appendix 484 2CDC508198D0211 Rev A AC S 1 x 1 13 2 Notes ...
Page 485: ...ABB i bus KNX Appendix AC S 1 x 1 2CDC508198D0211 Rev A 485 Notes ...
Page 486: ...ABB i bus KNX Appendix 486 2CDC508198D0211 Rev A AC S 1 x 1 Notes ...
Page 487: ......