AC/S 1.x.1 | 2CDC508198D0211 Rev. A 409
7.13.6
WebUI
Open the detailed view of the ASM by clicking the ASM's tile.
The operating type calculated is displayed on the web user interface. The outside temperature/supply
temperature present at the module is also displayed.
The "admin" and "expert" users can override the current operating type. For the other users this field is
dimmed and can therefore not be changed. The automatic calculation of the operating type continues to
run during the override and the automatically calculated operating type is also displayed on the web user
interface in "Auto". The operating type is only output in the group objects, on the ASM output sockets and
in the BACnet objects after the override has been cleared by selecting "Auto".
The override is active until it is cleared again.