ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 97
Multiplexer, 2 to 1 (1-MUX)
Selects a value from two input values.
Inputs
No.
DPT
Abbr.
Name
Visible
Description
1
1 bit
S
Selector
Always
2
Any
I
0
Input value
Always
3
Any
I
1
Input value
Always
Outputs
No.
DPT
Abbr.
Name
Visible
Description
1
Any
O
Result
Always
Parameters
Name
Value
Visible
Description
Send trigger
Yes
No
Always
Checkbox:
Yes: The output sends when the selector receives a
value.
No: The output does not send when selector receives
a value.
Function
If the selector has the value 1, input I
1
is sent to the output. If the selector has the value 0, input I
0
is sent
to the output.
Values received on unselected inputs are stored until the input is selected.
Whenever a telegram is received the output starts a recalculation independently if the value has changed.
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 476: ......
Page 482: ......
Page 484: ...ABB i bus KNX Appendix 484 2CDC508198D0211 Rev A AC S 1 x 1 13 2 Notes ...
Page 485: ...ABB i bus KNX Appendix AC S 1 x 1 2CDC508198D0211 Rev A 485 Notes ...
Page 486: ...ABB i bus KNX Appendix 486 2CDC508198D0211 Rev A AC S 1 x 1 Notes ...
Page 487: ......