ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 257
Pump
Settings for the heating distribution circuit's pump.
Double pump
Options:
No (checkbox cleared)
Yes (checkbox selected)
This parameter specifies whether a double pump or a single pump is used in the heating distribution
circuit. The group objects, BACnet objects, ASM sockets and the depiction on the web user interface are
adjusted to suit the setting.
Override by WebUI
Options:
No (checkbox cleared)
Yes (checkbox selected)
If this function is activated, the pump can be overridden via the web user interface. For this purpose
additional group objects are displayed that must be connected to the heating distribution circuit controller.
Pump display operating status
Options:
No (checkbox cleared)
Yes (checkbox selected)
If the pump outputs its operating status (Off/On), this status can be received by a group object via this
function and output on the web user interface, in a BACnet object and on the ASM socket.
Summary of Contents for i-bus KNX AC/S 1.x.1 Series
Page 1: ... PRODUCT MANUAL ABB i bus KNX AC S 1 x 1 Application Controller ...
Page 2: ......
Page 56: ......
Page 414: ...ABB i bus KNX Parameters 414 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 425: ...ABB i bus KNX Parameters AC S 1 x 1 2CDC508198D0211 Rev A 425 ...
Page 436: ...ABB i bus KNX Parameters 436 2CDC508198D0211 Rev A AC S 1 x 1 ...
Page 476: ......
Page 482: ......
Page 484: ...ABB i bus KNX Appendix 484 2CDC508198D0211 Rev A AC S 1 x 1 13 2 Notes ...
Page 485: ...ABB i bus KNX Appendix AC S 1 x 1 2CDC508198D0211 Rev A 485 Notes ...
Page 486: ...ABB i bus KNX Appendix 486 2CDC508198D0211 Rev A AC S 1 x 1 Notes ...
Page 487: ......