ABB i-bus
£
KNX
Commissioning
© 2010 ABB STOTZ-KONTAKT GmbH
105
No.
Function
Object name
Data type
Flags
16
Status fan speed
Fan
no EIS, 1 byte
DPT 5.010
C, R, T
The communication object is enabled if in parameter window
Status messages
the
parameter
Enable communication object "Status fan speed" 1 byte
is selected with option
yes
.
You can parameterise whether only the communication object value is updated or if they are
only sent on the bus after a change or on request. It is possible to parameterise if the actual
or required speed are displayed with the status object.
With this communication object it is possible for example to display the fan speed on the
display as a direct figure value.
The following telegram values apply for the 1 byte object:
Figure value
Hexadecimal
Binary value bit
76543210
Fan speed
0 00 00000000
0
(OFF)
1
01
00000001
Fan speed 1
2
02
00000010
Fan speed 2
3
03
00000011
Fan speed 3
17
Status fan speed 1
Fan
EIS 1, 1 bit
DPT 1.001
C, R, T
The communication object is enabled if in parameter window
Status messages
the
parameter
Enable communication object "Status fan speed x" 1 bit
is selected with option
yes
.
It is possible to parameterise if a communication object value is only updated and not sent,
sent on request, or only sent when changed.
Furthermore, you can parameterise if the status should indicate a current fan speed or
a required fan speed.
With this communication object is possible to display the fan speed in a visualisation or
to indicate it on a display.
Telegram value:
0 = fan speed OFF
1 = fan speed ON
18
Status fan speed 2
See communication object 17
19
Status fan speed 3
See communication object 17
20
Not assigned.