ABB i-bus
£
KNX
Commissioning
© 2010 ABB STOTZ-KONTAKT GmbH
107
No. Function
Object name
Data type
Flags
25 Forced
operation
Fan
EIS 1, 1 bit
DPT 1.003
C, W
The communication object is enabled if in parameter window
Direct operation
the
parameter
Enable communication object "Forced operation" 1 bit
has been selected
with the option
yes
.
If a forced operation is activated, the Fan Coil Actuator switches independently from the
control value and its parameterised Limitation 1…4 to forced operation.
The fan speed and valve position(s) during forced operation can be parameterised
individually from one another.
Telegram value:
0 = no forced operation
1 = forced operation
26 Automatic
ON/OFF
Fan
EIS 1, 1 bit
DPT 1.003
C, W
The communication object is enabled if in parameter window
Fan
the parameter window
Automatic operation
has been enabled.
If automatic mode is enabled, it will be activated on this communication object with the
value 1 after a download, bus reset or via a telegram.
Automatic mode is switched off, if a signal is received on a “manual communication object”.
During forced operation the automatic mode remains active; however, it is only operated
within the allowed limits.
If the value 1 is set in the parameter:
Telegram value:
0 = automatic operation OFF
1 = automatic operation ON
If the value 0 is set in the parameter:
Telegram value:
0 = automatic operation ON
1 = automatic operation OFF
27
Not assigned.
28 Status
automatic
Fan
EIS 1, 1 bit
DPT 1.003
C, R,
W
The communication object is enabled if in parameter window
Status messages
the
parameter
Enable communication object "Status automatic" 1 bit
is selected with option
yes
.
It is possible to parameterise if a communication object value is only updated and not sent,
sent on request, or only sent when changed.
The communication object indicates the status of the automatic mode.
Telegram value:
0 = inactive
1 = activated