ABB i-bus
£
KNX
Commissioning
© 2010 ABB STOTZ-KONTAKT GmbH
113
3.3.6
Valve HEATING
No.
Function
Object name
Data type
Flags
35 Block
Valve HEATING
EIS 1, 1 bit
DPT 1.003
C, W
The valve is blocked via this communication object.
If the block is enabled, it has the highest priority within the valve
HEATING
and the current
control value is retained, i.e. the valve remains stationary. Movement to a target position
which may not have yet been achieved will be performed to completion. If the block is
removed, the target position which has been set without the block is approached.
Telegram value:
0 = valve not blocked
1 = valve blocked
36 Forced
operation
Valve HEATING
EIS 1, 1 bit
DPT 1.003
C, W
This communication object sets the output in a defined state and blocks it. If the value 1 is
received, forced operation is activated and the output triggers the programmed valve
position. If the value 0 is received forced operation ends. The contact position is retained
until the FCA/S receives a new setting signal.
Telegram value:
0 = end forced operation
1 = start forced operation
37 Trigger
valve
purge
Valve HEATING
EIS 1, 1 bit
DPT 1.017
C, W
The valve purge is triggered using this communication object.
Telegram value:
0 = end valve purge, valve will be closed
1 = start valve purge, valve will be opened
Note for value 0
A purge currently underway is interrupted.
A purge not undertaken due to a higher priority will no longer be undertaken.
The purge cycle with automatic purge will be restarted
.