120
No.
Function
Object name
Data type
Flags
47 Disable
function
time
Output
EIS 1, 1 bit
DPT 1.003
C, W
This communication object is visible if in parameter window
Output General
the option
yes
has been selected in the
Enable staircase lighting time
parameter. The staircase lighting time
can be enabled or disabled via this communication object.
After bus voltage recovery, the communication object value with the parameter
Value object
"Disable function Time" on bus voltage recovery
can be determined in the parameter window
Output staircase lighting time
.
With a disabled function
Time
1, the output can only be switched on or off, the staircase
lighting time function will not be triggered.
Telegram value
1 = staircase light disabled
0 = staircase light enabled
The contact position at the time of disabling and enabling is retained and will only be
changed with the next switch command to the communication object
Switch
.
48
Change duration of
staircase lighting
Output
EIS 10, 2 byte
DPT 7.005
C, R, W
This communication object is visible if in the parameter window -
Time
the parameter
Enable
communication object “Change duration of staircase lighting” 2 byte
has been selected with
yes.
The staircase lighting time can changed via the bus using this communication object.
The time is defined in seconds.
The staircase lightning time which has already commenced is completed. A change of the
staircase lighting time is used the next time it is accessed.
With bus voltage failure the changed staircase lighting time is retained. Only after a complete
download of the application program, a version change, when the device has been
discharged or with an ETS reset, is the staircase lighting time duration overwritten with
the value set in the parameters.
49 Status
switch
Output
EIS 1, 1 bit
DPT 1.001
C, R, T
In the parameter window
Output
you can parameterise whether the communication object
value
no, update only
, after a change or
after request
is sent on the bus.
The communication object value directly indicates the current contact position of the
switching relay.
The status value can be inverted.
Telegram value
1 = relay ON or OFF depending on the parameterisation
0 = relay OFF or ON depending on the parameterisation