ABB i-bus
£
KNX
Commissioning
© 2010 ABB STOTZ-KONTAKT GmbH
91
Staircase lighting time
in s [0…65,535]
Options: 0…30…65,535
The staircase light defines how long the contact is closed, how long the light
remains on after an ON telegram.
The input is made in seconds.
Staircase lighting can be switched
Options:
ON with 1 and OFF with 0
ON with 1 no action with 0
ON with 0 or 1, switch OFF not possible
With this parameter you can set which telegram value is used to switch on
and prematurely switch off the staircase lighting.
x
ON with 0 or 1, switch OFF not possible
The function
Staircase lighting
is switched on independently of the value of the incoming telegram.
Premature switch off is not possible.
Enable communication object
“Change duration of staircase lighting” 2 byte
Options: no
yes
x
yes:
A 2 byte
Change duration of staircase lighting
communication
object is enabled. The staircase lighting time can be changed via the bus
with this. The value defines the staircase lighting time in seconds.
The staircase lightning time which has already commenced is
completed. A change of the staircase lighting time is used the next time
it is accessed.
x
no:
No modification of the staircase lighting time is possible via the bus.
Note
With bus voltage failure the changed staircase lighting time is saved.
Only after a renewed download of the application program is the staircase
lighting time overwritten.
How does the staircase light behave with bus voltage failure?
The behaviour at bus voltage failure is determined by the parameter
Reaction on bus voltage failure
in the parameter window
General
.
Summary of Contents for i-bus KNX FCA/S 1.1M
Page 1: ...ABB i bus KNX Fan Coil Actuator FCA S 1 1M Product Manual ...
Page 2: ......
Page 6: ......
Page 158: ......
Page 162: ...ABB i bus KNX Appendix 2010 ABB STOTZ KONTAKT GmbH 160 Notes ...
Page 163: ......