Commissioning
© 2010 ABB STOTZ-KONTAKT GmbH
97
3.3.3.2
Communication objects
HVAC System
1 Control value/4-pipe,
with switching object
No.
Function
Object name
Data type
Flags
30 Control
value
HEATING/COOLING
Control input
EIS 6, 1 byte
DPT 5.001
C, W
The communication object is enabled if in parameter window
Control input
the parameter
HVAC System
has been selected with the option
1 Control values/4-pipe, with switching
object
.
Using this communication object the control value HEATING or COOLING is predefined
as a 1 byte % value.
Telegram value:
0 % = OFF, no heating or cooling
100 % = ON, largest control value, maximum heating or cooling
31
not assigned.
32 Toggle
HEATING/COOLING
Control input
EIS 1, 1 bit
DPT 1.100
C, W
The communication object is enabled if in parameter window
Control input
the parameter
HVAC System
has been selected with the option
1 Control values/4-pipe, with switching
object
.
If the value 1 is set in the parameter:
Telegram value:
0 = COOLING activated
1 = HEATING activated
If the value 0 is set in the parameter:
Telegram value:
0 = HEATING activated
1 = COOLING activated
Note
If communication object 32
Toggle HEATING/COOLING – Control input
receives a value, the monitoring time is started.