Heating and cooling
with an additional stage: In addition to the heating and cooling
functions, one additional stage each with an autonomous controller type can be
programmed.
Note
This parameter is only available if the "Device function" parameter is set on
"Single device" or "Master device".
Pos: 31.7.4 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/ModuleAllgemein — Betriebsmodus nach Reset @ 40\mod_1421679113020_15.docx @ 312423 @ 3 @ 1
11.3.3
General - Operating mode after reset
Options:
Comfort
Standby
Eco mode
Cooling with additional stage
Frost/heat protection
After a reset the device will run in the operating mode after a restart until a new operating mode
is set as the result of device operation or by communication objects, as the case may be. This
operating mode should be defined during the planning phase. An improperly defined operating
mode can result in a loss of comfort or increased energy consumption.
–
Comfort
: If the room temperature is not automatically lowered and the room is therefore
controlled independent of its use.
–
Standby
: If the room is controlled automatically, e.g. by a presence detector, as a function of
its use.
–
Eco mode
: If the room is controlled automatically or manually as a function of it use.
–
Frost/heat protection
: If only the building protection function is necessary in the room after a
reset.
Note
This parameter is only available if the "Device function" parameter is set on
"Single device" or "Master device".
Pos: 31.7.5 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/ModuleAllgemein — Zusätzliche Funktionen @ 40\mod_1421679254855_15.docx @ 312438 @ 3 @ 1
11.3.4
General - Additional functions
Options:
No
Yes
– This parameter enables additional functions and communication objects, e.g. window
contact and presence detector.