KNX Technical Reference Manual
ABB-i-Bus
®
-KNX Millenium
Description of applications /
objects
KNX Technical Reference Manual | 1473-1-8681
— 58 —
Pos: 31.7.101 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Sollwerteinstellungen — aktuellen Sollwert senden @ 40\mod_1421742735380_15.docx @ 313649 @ 3 @ 1
11.3.81
Setpoint settings - Send current setpoint
Options:
Cyclic and during change
Only for change
The current setpoint value can be sent to the bus either cyclically and after a change, or only
after a change.
Pos: 31.7.102 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Sollwerteinstellungen — zyklisches Senden der aktuellen Solltemperatur (min) @ 40\mod_1421742783023_15.docx @ 313664 @ 3 @ 1
11.3.82
Setpoint settings - Cyclic sending of the current set-point temperature (min)
Options:
Setting option between 5 - 240
This parameter is used to specify the amount of time that will elapse before the current setpoint
value is automatically transmitted.
Note
This parameter is only available when the "Send current setpoint" is set on "Only
during change".
Pos: 31.7.103 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Sollwertverstellung @ 40\mod_1421743359507_15.docx @ 313679 @ 3 @ 1
11.3.83
Setpoint adjustment
Note
This parameter is only available if the "Device function" parameter is set on either
"Single device" or "Master device".
Pos: 31.7.104 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Sollwertverstellung — max. manuelle Anhebung beim Heizbetrieb (0 - 15°C) @ 40\mod_1421743407728_15.docx @ 313694 @ 3 @ 1
11.3.84
Setpoint adjustment — Maximum manual increase during heating mode (0 - 15°C)
Options:
Setting option between 0 - 15
This preset can be used to limit the manual increase during heating.
Note
This parameter is only available when the "Control function" parameter is set on
"Heating", "Heating with additional stage", "Heating and cooling" or "Heating and
cooling with additional stages".
Pos: 31.7.105 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Sollwertverstellung — max. manuelle Absenkung beim Heizbetrieb (0 - 15°C) @ 40\mod_1421743479241_15.docx @ 313709 @ 3 @ 1
11.3.85
Setpoint adjustment — Maximum manual reduction during heating mode (0 - 15°C)
Options:
Setting option between 0 - 15
This preset can be used to limit the manual decrease during heating.
Note
This parameter is only available when the "Control function" parameter is set on
"Heating", "Heating with additional stage", "Heating and cooling" or "Heating and
cooling with additional stages".