KNX Technical Reference Manual
ABB-i-Bus
®
-KNX Millenium
Description of applications /
objects
KNX Technical Reference Manual | 1473-1-8681
— 59 —
Pos: 31.7.106 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Sollwertverstellung — max. manuelle Anhebung beim Kühlbetrieb (0 - 15°C) @ 40\mod_1421743538138_15.docx @ 313724 @ 3 @ 1
11.3.86
Setpoint adjustment — Maximum manual increase during cooling mode (0 - 15°C)
Options:
Setting option between 0 - 15
This preset can be used to limit the manual increase during cooling.
Note
This parameter is only available when the "Control function" parameter is set on
"Cooling", "Cooling with additional stage", "Heating and cooling" or "Heating and
cooling with additional stages".
Pos: 31.7.107 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Sollwertverstellung — max. manuelle Absenkung beim Kühlbetrieb (0 - 15°C) @ 40\mod_1421743637040_15.docx @ 313739 @ 3 @ 1
11.3.87
Setpoint adjustment — Maximum manual reduction during cooling mode (0 - 15°C)
Options:
Setting option between 0 - 15
This preset can be used to limit the manual decrease during cooling.
Note
This parameter is only available when the "Control function" parameter is set on
"Cooling", "Cooling with additional stage", "Heating and cooling" or "Heating and
cooling with additional stages".
Pos: 31.7.108 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Sollwertverstellung — Zurücksetzen der manuellen Verstellung bei Empfang eines Basissollwertes @ 40\mod_1421743723193_15.docx @ 313754 @ 3 @ 1
11.3.88
Setpoint adjustment - Resetting of the manual adjustment for receipt of a basic setpoint
Options:
No
Yes
Activating this parameter will cause the manual adjustment to be deleted and the new setpoint
value to be provided when a new value is received via the "Basic setpoint" object.
If the parameter is deactivated, the manual adjustment is added to the new base setpoint value.
Example: Previous base setpoint value of 21°C + manual adjustment of 1.5°C = 22.5°C. The
object receives a new basic setpoint of 18°C plus the previous manual adjustment of 1.5°C for a
total of 19.5°C.