11.3.93
Temperature reading - Inputs of weighted temperature reading
Options:
Internal and external measurement
2 x external measurement
Internal and 2x external measurement
Specifies the temperature reading inputs for the weighted measurement, in which the calculated
weighted average of the inputs is used as an input value for control
Note
This parameter is only available when the "Inputs of temperature reading"
parameter is set on "Weighted measurement".
Pos: 31.7.116 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Temperaturerfassung — Gewichtung der internen Messung (0..100%) @ 40\mod_1421744843727_15.docx @ 313844 @ 3 @ 1
11.3.94
Temperature reading - Weighting of internal measurement (0 to 100%)
Options:
Setting option between 0 - 15
Specifies the weighting of the internal measurement at a level between 0% and 100%.
Note
This parameter is only available when the "Inputs of weighted temperature
reading" parameter is set on "Internal and external measurement" or "Internal and
2x external measurement".
Pos: 31.7.117 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Temperaturerfassung — Gewichtung der externen Messung (0..100%) @ 40\mod_1421744895847_15.docx @ 313859 @ 3 @ 1
11.3.95
Temperature reading - Weighting of external measurement (0 to 100%)
Options:
Setting option between 0 - 15
Specifies the weighting of the external measurement at a level between 0% and 100%.
Note
This parameter is only available when the "Inputs of weighted temperature
reading" parameter is set on "Internal and external measurement","2x external
measurement" or "Internal and 2x external measurement".
Pos: 31.7.118 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Temperaturerfassung — Gewichtung der externen Messung 2 (0..100%) @ 40\mod_1421745031552_15.docx @ 313874 @ 3 @ 1
11.3.96
Temperature reading - Weighting of external measurement 2 (0 to 100%)
Options:
Setting option between 0 - 15
Specifies the weighting of the external measurement 2 at a level between 0% and 100%. When
added together with the (0%...100%) weighting of the external measurement, the result must be
100%.
Note
This parameter is only available when the "Inputs of weighted temperature
reading" parameter is set on "2x external measurement" or "Internal and 2x
external measurement".