KNX Technical Reference Manual
ABB-i-Bus
®
-KNX Millenium
Description of applications /
objects
KNX Technical Reference Manual | 1473-1-8681
— 78 —
Pos: 31.11.17 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Kommunikationsobjekte/Objekt-RTR / RTR/Module/Betriebsmodus überlagert @ 41\mod_1422461351816_15.docx @ 329926 @ 3 @ 1
11.5.13
Superimposed operating mode
Number
Name
Object function
Data type
13
1. Superimposed operating
mode
Input
HVAC mode
2. Superimposed operating
mode (master/slave)
Input
HVAC mode
The "Superimposed operating mode" object receives the operating mode that is to be set as 1-
byte value. Here value 0 means "Superimposition inactive", value 1 "Comfort", value 2
"Standby", value 3 "Economy" and value 4 "Frost/heat protection".
In addition to manual setpoint adjustment and the adjustment of the basic setpoint value, the
setpoint temperature of the controller can also be defined by objects "Superimposed operating
mode", "Condensate ware alarm", "Dew alarm", "Window contact", "Control On/Off", "Presence
detector" and "Operating mode (listed in decreasing order of priority).
Note
Item 2:
If the master/slave mode is active, the "Superimposed operating mode" object of
the master and the slave must be connected to the group address of the
transmitter.
Pos: 31.11.18 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Kommunikationsobjekte/Objekt-RTR / RTR/Module/Fensterkontakt @ 41\mod_1422461410317_15.docx @ 329942 @ 3 @ 1
11.5.14
Window contact
Number
Name
Object function
Data type
14
1. Window contact
Input
Switching
2. Window contact
(master/slave)
Input
Switching
The object uses the value 1 to signal an open window to the controller. If no other object with a
higher priority is present, then the "Window contact" message causes the controller to be set to
the setpoint value for frost/heat protection. In addition to manual setpoint adjustment and the
adjustment of the basic setpoint value, the setpoint temperature of the controller can also be
defined by objects "Superimposed operating mode", "Condensate water alarm", "Dew alarm",
"Window contact", "Control On/Off", "Presence detector" and "Operating mode (listed in
decreasing order of priority).
Note
Item 2:
If the master/slave mode is active, the "Window contact (master/slave)" object of
the master and the slave must be connected to the group address of the
transmitter.