KNX Technical Reference Manual
ABB-i-Bus
®
-KNX Millenium
Description of applications /
objects
KNX Technical Reference Manual | 1473-1-8681
— 90 —
Pos: 31.15 /Layout bis 2014-11-11/Online-Dokumentation (+KNX)/Überschriften (--> Für alle Dokumente <--)/2. Ebene/A - F/Applikationen "Taste oben rechts" @ 41\mod_1422535402439_15.docx @ 331379 @ 2 @ 1
11.7
Applications for "Button top right"
Pos: 31.16 /Layout bis 2014-11-11/Online-Dokumentation (+KNX)/Applikations- / Objektbeschreibungen/KNX/KNX-Sensorik/Millenium/6125-26-29-IR - Bedienelement/Applikationen "Bedienelement mit Multifunktion"/Applikation "1-Tasten-Schalten" @ 41\mod_1422540023693_15.docx @ 331413 @ 2 @ 1
11.7.1
Application "1-button switching"
When actuated or released a switching telegram is sent out. In each case, the application makes a separate set
of parameters and communication objects available for the 1st and the 2nd button. The other side of the button
can be assigned a further "button-oriented" function.
Parameters
General parameter
Settings
Comments
Reaction on rising edge
• On
• Off
• alternating on/off
• no reaction
–
Reaction on falling edge
• On
• Off
• alternating on/off
• no reaction
–
Objects
No.
Object name
Data type
Flags
0
Switching
1 Bit EIS1 / DPT 1.001
C, W ,T ,U
Pos: 31.17 /Layout bis 2014-11-11/Online-Dokumentation (+KNX)/Applikations- / Objektbeschreibungen/KNX/KNX-Sensorik/Millenium/6125-26-29-IR - Bedienelement/Applikationen "Bedienelement mit Multifunktion"/Applikation "1-Tasten-Dimmen" @ 41\mod_1422540166803_15.docx @ 331447 @ 2 @ 1
11.7.2
Application "1-button dimming"
The push-buttons have communication objects for switching and dimming. A distinction is made between a short
(switching) and long (dimming) press of the button. In each case, the application makes a separate set of
parameters and communication objects available for the 1st and the 2nd button. The application allows a lamp to
be dimmed with the one button and the other button to be assigned with other "button-oriented" functions.
Parameters
General parameter
Settings
Comments
Duration of long operation (s)
Time input from 0.3 to 3.0 seconds
General
Working mode of the buttons for switching
• deactivated
• Off
• On
• alternating on/off
Advanced
Working mode of the buttons for dimming
• alternating brighter/darker
• darker
• brighter
Objects
No.
Object name
Data type
Flags
0
Switching
1 Bit EIS2 / DPT 1.001
C, W ,T ,U
1
relative dimming
4 Bit EIS2 / DPT 3.007
C, T