KNX Technical Reference Manual
ABB-i-Bus
®
-KNX Millenium
Description of applications /
objects
KNX Technical Reference Manual | 1473-1-8681
— 94 —
Objects
No.
Object name
Data type
Flags
0
Switching (rising edge) (1 bit)
1 Bit EIS1 / DPT 1.001
C, W ,T ,U
Switching (rising edge) (1-byte 0..100%)
1 Byte EIS6 / DPT 5.001
C, W ,T ,U
Switching (rising edge) (1-byte 0..255)
1 Byte EIS14 / DPT 5.010
C, W ,T ,U
Switching (rising edge) (2-byte float)
2 Byte EIS5 / DPT 9.xxx
C, W ,T ,U
Switching (rising edge) (2-byte signed)
2 Byte EIS10 / DPT 7.001
C, W ,T ,U
Switching (rising edge) (2-byte unsigned)
2 Byte EIS10 / DPT 8.001
C, W ,T ,U
Switching (rising edge) (4-byte float)
4 Byte EIS9 / DPT 14.xxx
C, W ,T ,U
Switching (rising edge) (4-byte signed)
4 Byte EIS11 / DPT 13.001
C, W ,T ,U
Switching (rising edge) (4-byte unsigned)
4 Byte EIS11 / DPT 12.001
C, W ,T ,U
1
Switching (falling edge) (1 bit)
1 Bit EIS1 / DPT 1.001
C, W ,T ,U
Switching (falling edge) (1-byte 0..100%)
1 Byte EIS6 / DPT 5.001
C, W ,T ,U
Switching (falling edge) (1-byte 0..255)
1 Byte EIS14 / DPT 5.010
C, W ,T ,U
Switching (falling edge) (2-byte float)
2 Byte EIS5 / DPT 9.xxx
C, W ,T ,U
Switching (falling edge) (2-byte signed)
2 Byte EIS10 / DPT 7.001
C, W ,T ,U
Switching (falling edge) (2-byte unsigned)
2 Byte EIS10 / DPT 8.001
C, W ,T ,U
Switching (falling edge) (4-byte float)
4 Byte EIS9 / DPT 14.xxx
C, W ,T ,U
Switching (falling edge) (4-byte signed)
4 Byte EIS11 / DPT 13.001
C, W ,T ,U
Switching (falling edge) (4-byte unsigned)
4 Byte EIS11 / DPT 12.001
C, W ,T ,U
Pos: 31.20 /Layout bis 2014-11-11/Online-Dokumentation (+KNX)/Applikations- / Objektbeschreibungen/KNX/KNX-Sensorik/Millenium/6125-26-29-IR - Bedienelement/Applikationen "Bedienelement mit Multifunktion"/Applikation "1-Tasten-Lichtszenennebenstelle mit Speicherfunktion" @ 41\mod_1422540212387_15.docx @ 331481 @ 2 @ 1
11.7.5
Application "1-button light scene extension unit with memory function"
When a button is actuated a predefined light scene number is called up. In each case, the application makes a
separate set of parameters and communication objects available for the 1st and the 2nd button. The application
makes it possible to call up a light scene via one button side while the other button side can be assigned with a
further "button-oriented" function. The user has the option to trigger a light scene memory command via a long
actuation of the button.
Parameters
General parameter
Settings
Comments
Duration of long operation (s)
Time input from 0.3 to 10.0 seconds
Only available when parameter "Storage
function light scenes" is set on "activated".
Storage function light scenes
• deactivated
• activated
–
Number of light scene
1 … 64
–
Objects
No.
Object name
Data type
Flags
0
Number of light scene
1 Byte EIS6 / DPT 18.001
C, T