ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
103
Cyclic monitoring time in s
[0…65,535, 0 = no monitoring]
Options: 0…65,535
The parameter defines the intervals at which the safety operation is
monitored. The safety operation is not monitored with the setting 0.
If the communication object
Safety operation A
does not receive a
telegram after the set monitoring time the safety is activated.
Note
The safety operation is reset if an ETS reset has occurred.
Important
On bus voltage recovery the safety operation remains active until
the enable is sent again.
Safety operation B active
Options: no
yes
This parameter defines how the safety operation B is activated.
Note
The setting options for safety operation B do not differ from those of safety
operation A, see above.
Position with cancelling of the safety operation.
Options: unchanged
UP
DOWN
STOP
move to saved position
This parameter defines the position to which the shutter/blind moves after
safety operation is cancelled.
•
Unchanged:
The shutters remain unchanged in its position and/or the
current movement action is completed.
•
UP:
The shutter moves UP.
•
DOWN:
The shutter moves DOWN.
•
STOP:
The output is electrically disconnected, i.e. a moving shutter is
stopped.
•
move to saved position:
The shutter is moved to its preset position.